Nurse Call
Nurse call commissioning
100% functional test of every device and call type.
- Site
- Date
- Technician
- Reference
Every room
- Patient call from handset: correct room and bed on light, display, and handset
- Bathroom pull cord: higher-priority indication; cord reaches near floor
- Presence and cancel work only at the point of call
- Staff assist and emergency calls show correct priority
- Handset disconnection raises a fault or call
- Two-way speech clear (where fitted)
System
- Higher-priority calls override lower ones
- Escalation timings match the clinical team's agreement
- Day/night zone changes work
- Calls reach DECT / Wi-Fi handsets with correct text; accept and reject work
- Fire alarm interface displays correctly and cannot affect the fire system
Resilience
- Disconnect a device, bus, and network switch: faults reported
- Mains removed: system runs on backup for the required time
- Log shows test calls with accurate times
Acceptance
- Clinical staff confirm tones, locations, zoning, and escalation
- Device schedule, test sheets, drawings, and backup handed over
- User training records signed
Notes / defects
Technician signature
Client / supervisor signature